Summary
AC System Losses account for power dissipation in the AC electrical infrastructure between the inverter output and the point of interconnection. After AC degradation is applied (if Linear AC or Stepped AC selected), PlantPredict calculates losses in the following sequence: (1) Auxiliary Loads (DAS, cooling, tracker motors), (2) MV Transformer, (3) AC Collection System, (4) HV Equipment (transformers and transmission lines), (5) Availability Loss, and (6) Grid Limit. Both MV and HV transformers use the same quadratic loss model. AC Collection uses a quadratic (Version 12+) or flat percentage (Versions 3-11) loss model.Inputs
| Name | Symbol | Units | Description |
|---|---|---|---|
| AC Power Input | W | Total AC power from inverters (after degradation) | |
| DAS Load | W | Data acquisition system power consumption | |
| Cooling Load | W | Inverter/equipment cooling power consumption | |
| Tracker Motor Load | W | Tracker motor power consumption | |
| MV Transformer Rating | kVA | Array-level transformer capacity | |
| MV No-Load Loss | — | MV transformer no-load loss fraction | |
| MV Full-Load Loss | — | MV transformer full-load loss fraction | |
| AC Collection Loss Fraction | — | Collection system loss fraction | |
| AC Power Rated | W | Total inverter rated capacity for array | |
| HV Transformer Rating | kVA | High-voltage transformer capacity | |
| HV No-Load Loss | — | HV transformer no-load loss fraction | |
| HV Full-Load Loss | — | HV transformer full-load loss fraction | |
| Line Voltage | V | Transmission line voltage | |
| Line Length | feet | Transmission line length | |
| Resistance | mΩ/ft | Resistance per conductor per unit length | |
| Conductors Per Phase | — | Parallel conductors per phase | |
| Power Factor | — | System power factor | |
| Availability Loss | % | Availability loss percentage | |
| Maximum Plant Output | W | POI capacity limit (LGIA) |
Outputs
| Name | Symbol | Units | Description |
|---|---|---|---|
| Power After Auxiliary Loads | W | Power after auxiliary load deductions | |
| MV Transformer Output | W | Power after MV transformer losses | |
| AC Collection Output | W | Power after AC collection losses | |
| HV Equipment Output | W | Power after HV transformer and transmission losses | |
| Post-Availability Power | W | Power after availability losses | |
| Grid-Limited Power | W | Final power after grid limit clipping |
Detailed Description
Array-Level Losses
Auxiliary Load Losses
Auxiliary loads are deducted from the degraded AC power output before transformer losses: where:- is the data acquisition system load (constant when energized)
- is the inverter/equipment cooling load (applied when power output is positive)
- is the tracker motor load (applied when power output is positive)
MV Transformer Losses
The MV transformer uses a quadratic loss model (see Transformer Loss Model):AC Collection System Losses
AC Collection System losses are calculated after the MV transformer. Version 12+ (Quadratic Loss Model): Loss scales quadratically with power flow, representing I²R characteristic of conductor losses. Versions 3-11 (Flat Percentage Model): Daytime operation (): Nighttime operation (): Nighttime formula accounts for power drawn from grid to energize transformers, with losses applied both to incoming power and additional draw from grid. Array Output Aggregation: Array outputs are aggregated to block level: Rated capacity is sum of all inverter kVA ratings in the array:Plant-Level Losses
HV Equipment Losses
Sum power from all blocks (after AC collection): HV transformers and transmission lines are applied in user-defined ordinal sequence. HV Transformer: Transmission Line: Final HV equipment output:Availability Loss
Grid Limit (Capacity Limit)
If LGIA limitation enabled: If LGIA time series enabled, varies by timestep.Transformer Loss Model
Used for both MV and HV transformers. Loss components: Quadratic loss equation: Version 3: Requires: and Version 4+: Same formula but requires: Nighttime disconnect: If nighttime disconnect triggered, for MV transformer. Output power:Transmission Line Loss Model
Total line resistance (SI units): Phase current: Three-phase power loss: Output power:HV Equipment Sequence
HV transformers and transmission lines are applied in an ordinal sequence defined by the user. Each piece of equipment is assigned a sequence number, and losses are calculated in ascending order. Voltage Selection for Transmission Lines: The voltage used for transmission line loss calculations depends on the equipment sequence:- If the transmission line is the first piece of HV equipment (no prior HV transformer), the voltage is set to the highest secondary voltage among all MV transformers in the plant.
- If an HV transformer precedes the transmission line in the sequence, the voltage is set to the high-side (secondary) voltage of that transformer.
References
- King, D. L., Boyson, W. E., & Kratochvil, J. A. (2004). Photovoltaic array performance model. SAND2004-3535, Sandia National Laboratories.