Summary
The maximum AC power sets the upper bound for the operating region logic, determining the threshold. The AC power setpoint is defined in the inverter configuration from the nameplate rating and the design derate factor. Alternatively, the setpoint or the derate factor can be set per timestep using a user-uploaded time series. When manufacturer derate curves are provided, the setpoint may be further reduced depending on ambient temperature and site elevation.Inputs
Outputs
Detailed Description
Setpoint Determination
The AC power setpoint is the baseline upper bound on inverter output. It is derived from the inverter nameplate rating and the user-configured design derate: A design derate of uses the full nameplate; lower values curtail the inverter (e.g., limits output to 95% of rated capacity). The user can set either the design derate or the absolute setpoint ; the other value is adjusted automatically to satisfy the equation above. Both values can also be overridden on a per-timestep basis by uploading a time series. A setpoint time series provides directly in kVA, while a derate time series provides as a ratio (0 to 1). If both are configured, the setpoint time series takes priority.Curve Selection by Elevation

Example Inverter Temperature / Elevation Derate Curves