Summary
Array-Level AC Losses account for power dissipation between the inverter output and the AC collection system output, calculated independently for each array. The loss chain proceeds in sequence: auxiliary load deductions, MV transformer losses, and AC collection system losses. Array outputs are then aggregated to the block level using repeater counts.Inputs
| Name | Symbol | Units | Description |
|---|---|---|---|
| Degraded AC Power | W | AC power after degradation (from AC degradation) | |
| DAS Load | W | Data acquisition system power consumption | |
| Cooling Load | W | Inverter/equipment cooling power consumption | |
| Tracker Motor Load | W | Tracker motor power consumption | |
| MV Transformer Rating | kVA | Array-level transformer nameplate capacity | |
| MV No-Load Loss | — | MV transformer no-load loss fraction | |
| MV Full-Load Loss | — | MV transformer full-load loss fraction | |
| AC Collection Loss | — | AC collection system loss fraction |
Outputs
| Name | Symbol | Units | Description |
|---|---|---|---|
| Block Power | W | Aggregated AC power at block level, after all array-level losses |
Detailed Description
Auxiliary Loads
Auxiliary loads are constant power deductions subtracted from the degraded AC power before transformer losses: The DAS load is applied whenever the system is energized. Cooling and tracker motor loads are applied only when inverter power output is positive. When nighttime disconnect is triggered (all inverters in the array are in shutdown or low-power regions), all auxiliary loads are set to zero.MV Transformer
The MV transformer applies the shared Transformer Loss Model to : where is computed from the quadratic loss equation using , , and . If the transformer is disabled for the array, and . During nighttime disconnect, the transformer no-load loss is set to zero, eliminating standby core losses.AC Collection System
AC collection losses represent resistive (I²R) losses in the medium-voltage cabling between the MV transformer and the plant-level collection point. Version 12+ (Quadratic Model): Loss scales quadratically with power flow, reflecting the I²R characteristic of conductor losses: where is the total inverter rated capacity for the array: Versions 3–11 (Flat Percentage Model): During daytime operation (): During nighttime operation (), the system draws power from the grid to keep transformers energized. Losses are applied to both the consumed power and the additional grid draw: In both versions, the AC collection output is:Block Aggregation
Array outputs are aggregated to the block level using repeater counts:References
- IEEE Std C57.12.00. IEEE Standard for General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers.